XBD-L Fire fighting Horizontal water Booster portable fire pump set
Specific parameters
Pump Flow rate: 5~80L/s |
Head :5 ~ 125 m |
Power: 1.5 ~ 200 kw |
Max working pressure: ≤1.6Mpa |
Medium temperture: -15oC to 120oC |
Diameter range: 50 ~ 250 mm |
Rotate speed :1480 to 2900 RPM |
Features:
a)Compact structure
b)Stable running, low noise
c)No leakage
d)Convenient operation
e)Viewing from the inlet of the pump, the outlet of it can be mounted in one of the three ways, horizontally leftward, vertically upward and horizontally rightward
Application area
fire hydrant water | the turbo-charged air conditioning refrigeration system |
fire-fighting system | heating, the bathroom changes in temperature water cycle |
industry and city | high-rise construction turbo-charged |
water spray system | boiler changes in temperature water cycle |
water supply | the long-distance range to supply water |
Specification performance data table
model | capacity | pressure | speed | power | effeciency | npsh | weight |
Q (L/s) | P (MPa) | n(r/min) | N(Kw) | (%) | (NPSH)r(m) | (Kg) | |
XBD3.2/5-65L-160 | 5 | 0.32 | 2900 | 4 | 63 | 2.5 | 75 |
XBD5/5-65L-200 | 5 | 0.5 | 2900 | 7.5 | 58 | 2.5 | 107 |
XBD8/5-65L-250 | 5 | 0.8 | 2900 | 15 | 50 | 2.5 | 180 |
XBD12.5/5-65L-315 | 5 | 1.25 | 2900 | 30 | 40 | 2.5 | 320 |
XBD3.2/10-80L-160 | 10 | 0.32 | 2900 | 7.5 | 69 | 3 | 105 |
XBD5/10-80L-200 | 10 | 0.5 | 2900 | 15 | 65 | 3 | 175 |
XBD8/10-80L-250 | 10 | 0.8 | 2900 | 22 | 57 | 3 | 240 |
XBD12.5/10-80L-315 | 10 | 1.25 | 2900 | 37 | 54 | 3 | 355 |
XBD3.2/25-100L-160 | 25 | 0.32 | 2900 | 15 | 74 | 4.5 | 191 |
XBD5/25-100L-200 | 25 | 0.5 | 2900 | 22 | 72 | 4 | 245 |
XBD8/25-100L-250 | 25 | 0.8 | 2900 | 37 | 67 | 4 | 345 |
XBD12.5/25-100L-315 | 25 | 1.25 | 2900 | 75 | 66 | 4 | 689 |
XBD3.2/40-125L-160 | 40 | 0.32 | 2900 | 22 | 76 | 4 | 265 |
XBD5/40-125L-200 | 40 | 0.5 | 2900 | 37 | 75 | 5.5 | 395 |
XBD8/40-125L-250 | 40 | 0.8 | 2900 | 55 | 73 | 5 | 580 |